UL10070 AC600V 105℃ FT2 Flame Test Single Core PVC Insulation 16 AWG Wire
- Cable Type : UL10070
- Standard : UL758,UL1581
- Rated Voltage : AC600V
- Rated Temperature: 105℃
- Flame Test : FT2,FT1,VW-1
- Conductor:Bare or Tinned Copper Stranded
- Insulation : PVC
- RoHS & Reach : Approval
- Certificate : UL,CUL
Description
UL10070 AC600V 105℃ FT2 Flame Test Single Core PVC Insulation 16 AWG Wire
• UL certificate, Compliant with UL758 Standard
• Rating : 105 deg C, 600 Vac, Horizontal flame.
• Conductor : 18 AWG – 4/0 AWG, solid or stranded, consisting of 40-20 AWG stranding. May be braided
• Insulation : Extruded PVC
• Use : Internal Wiring of Appliances
| Conductor size | Insulation Minimum average thickness |
Insulation Minimum thickness at any point |
| 18 – 9 AWG | 30 mils | 27 mils |
| 8-7 AWG | 45 mils | 40 mils |
| 6-2 AWG | 60 mils | 54 mils |
| 1-4/0 AWG | 80 mils | 72 mils |
| Conductor | Insulation | Max Resistance (Ω/km, 20°C, DC) |
|||
| AWG | No./mm | Nom.Dia. (mm) |
Nom.Thick. (mm) |
Nom.Dia. (mm) |
|
| 18 | 41/0.16 | 1.18 | 0.76 | 3.78 | 21.8 |
| 16 | 26/0.254 | 1.49 | 0.76 | 3.1 | 14.64 |
| 14 | 41/0.254 | 1.88 | 0.76 | 3.5 | 9.25 |
| 12 | 65/0.254 | 2.36 | 0.76 | 4 | 5.82 |
| 10 | 105/0.254 | 3 | 0.76 | 4.6 | 3.66 |
| 9 | 131/0.254 | 3.7 | 0.76 | 5.3 | 2.96 |
| 8 | 168/0.254 | 4.2 | 1.14 | 6.5 | 2.35 |
| 7 | 210/0.254 | 4.7 | 1.14 | 7 | 1.87 |
| 6 | 266/0.254 | 5.3 | 1.52 | 8.4 | 1.48 |
| 5 | 329/0.254 | 5.8 | 1.52 | 9 | 1.17 |
| 4 | 420/0.254 | 6.6 | 1.52 | 9.7 | 0.928 |
| 3 | 532/0.254 | 7.5 | 1.52 | 10.5 | 0.744 |
| 2 | 665/0.254 | 8.4 | 1.52 | 11.5 | 0.59 |
| 1 | 836/0.254 | 9.4 | 2.03 | 13.5 | 0.467 |
| 1/0 | 1045/0.254 | 10.5 | 2.03 | 14.6 | 0.37 |
| 2/0 | 1330/0.254 | 11.9 | 2.03 | 16 | 0.297 |
| 3/0 | 1672/0.254 | 13 | 2.03 | 17.5 | 0.236 |
| 4/0 | 2109/0.254 | 14.7 | 2.03 | 19.1 | 0.187 |