UL1007 AC300V 60℃ or 80℃ FT2 Flame Test Single Core PVC Insulated Electric Wire
- Cable Type : UL1007
- Standard : UL758
- Rated Voltage : AC 300V
- Rated Temperature: 60℃ or 80℃
- Flame Test : FT2
- Conductor:Bare or Tinned Copper Stranded
- Insulation : PVC
- RoHS & Reach : Approval
- Certificate : UL,CUL
Description
UL1007 AC300V 60℃ or 80℃ FT2 Flame Test Single Core PVC Insulated Electric Wire
• UL certificate, Compliant with UL758 Standard
• Rating : 80 deg C, 300 Vac, Horizontal flame. Optional – 60 deg C or 80 deg C Oil.
• Conductor : 32 AWG – 16 AWG, Solid or Stranded.
• Insulation : Extruded PVC, 15 mils minimum average thickness, 13 mils minimum thickness at any point , Uniform insulation thickness for easy stripping and cutting, Passed FT2 flame test
• Internal wiring of appliances. Tags may indicate the following: 600 V Peak – For Electronic Use Only.
| Conductor | Insulation | Max Resistance (Ω/km, 20°C, DC) |
|||
| AWG | No./mm | Nom.Dia. (mm) |
Nom.Thick. (mm) |
Nom.Dia. (mm) |
|
| 26 | 1/0.404 | 0.4 | 0.4 | 1.2 | 142.79 |
| 7/0.16 | 0.48 | 0.41 | 1.3 | 148.94 | |
| 24 | 1/0.511 | 0.51 | 0.41 | 1.33 | 89.39 |
| 11/0.16 | 0.61 | 0.41 | 1.43 | 93.25 | |
| 22 | 1/0.643 | 0.64 | 0.41 | 1.46 | 54.3 |
| 17/0.16 | 0.76 | 0.41 | 1.58 | 55 | |
| 20 | 1/0.813 | 0.81 | 0.41 | 1.65 | 33.9 |
| 26/0.16 | 0.94 | 0.41 | 1.76 | 34.6 | |
| 18 | 1/1.024 | 1.02 | 0.41 | 1.85 | 21.4 |
| 41/0.16 | 1.18 | 0.41 | 2 | 21.8 | |
| 16 | 26/0.254 | 1.49 | 0.41 | 2.32 | 14.64 |