UL83 Standard THHN THWN THWN-2 600V 90℃ Single Core Thermoplastic Insulated Wires and Cables

  • Cable Type : THHN THWN THWN-2
  • Standard : UL83
  • Conductor:Bare or Tinned Copper, Stranded or Solid
  • Insulation : PVC
  • Rated Voltage: AC 600V
  • Rated Temperature : ~40℃~90℃
  • RoHS & Reach : Approval
  • Certificate : UL

Description

UL83 Standard THHN THWN THWN-2 600V 90℃ Single Core Thermoplastic Insulated Wires and Cables

  Standard : UL83

  UL83 Standard Thermoplastic-Insulated Wires and Cables : THHN THWN THWN-2

  Type THHN THWN THWN-2 is suitable for various commercial and industrial applications.These cables may be installed in wet or dry locations , indoors or outdoors ,in raceways ,underground ducts.They are permitted for 600V application

  THHN is rated at a conductor temperature of 90℃ dry
  THWN is rated at a conductor temperature of 75℃ wet or 90℃ dry
  THWN-2 is rated at a conductor temperature of 90℃ wet or dry.

Conductor Insulation
AWG No./mm Nom.Dia. (mm) Nom.Thick. (mm) Nom.Dia. (mm)
14AWG 7/0.62 1.86 0.38 2.88
12AWG 7/0.77 2.31 0.38 3.33
10AWG 7/0.98 3.09 0.51 4.24
8AWG 7/1.23 4 0.76 5.69
6AWG 7/1.56 4.93 0.76 6.68
4AWG 7/1.96 6.3 1.02 8.42
3AWG 19/1.336 7.5 1.02 8.79
2AWG 7/2.47 7.82 1.02 9.95
1AWG 19/1.686 8.95 1.27 11.05
1/0AWG 19/1.89 9.9 1.27 12.51
2/0AWG 19/2.13 11.3 1.27 13.71
3/0AWG 19/2.39 12.17 1.27 15.01
4/0AWG 19/2.68 13.62 1.27 16.46
250Kcmil 37/2.09 14.91 1.52 18.25
350Kcmil 37/2.47 17.57 1.52 20.91
400Kcmil 37/2.64 18.76 1.52 22.1
500Kcmil 37/2.95 20.93 1.52 24.27
750Kcmil 61/2.82 25.74 1.78 29.6

 

 

 

Pls send your message to us